ABB CM-ENS Series Liquid Level Relay - DIN Rail Mount, 24 240 V ac/dc 1 Voltage Input SPDT Relay

  • RS Stock No. 135-6328
  • Mfr. Part No. 1SVR730850R0300
  • Manufacturer ABB
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
COO (Country of Origin): DE
Product Details

CM-ENS Liquid Level Relays

A series of liquid level control relays from ABB for conductive liquids. The CM-ENS range gives a choice of 3 variants each with a compact, space saving housing with the highest fire protection and environmentally friendly materials. Installation is quick and easy using screw or easy-connect terminals and tool free DIN Rail mounting.

Features and Benefits (CM-ENS.1 / CM-ENS.2 / CM-ENS.3)

• 3 LED operational state indication • Choices of Easy connect push in terminals or screw terminals
• DIN Rail mountable - no tooling required
• Easy adjustment using front panel
• Cascadable
• Adjustable response sensitivity
• 1 C/O SPDT output contact
• Compact 22.5 mm width

Additional Features CM-ENS.2

• Control of two levels (MIN/MAX) • Front panel adjustment of fill and drain function

Additional Features CM-ENS.31

• Control of two levels (MIN/MAX) • Front panel adjustment of fill and drain function
• 2 C/O SPDT Contacts
• Selectable ON / OFF delay

Applications

• Dry running protection • Overflow protection
• Liquid level control

Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.

Application Examples

Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:

Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels

Specifications
Attribute Value
Number of Inputs 1
Mounting Style DIN Rail Mount
Supply Voltage 24 240 V ac/dc
Overall Length 113.4mm
Overall Width 22.5mm
Overall Depth 113.4mm
Minimum Operating Temperature -25°C
Maximum Operating Temperature +60°C
Sensitivity 0.1 1000 kΩ
Isolation Voltage 300 (Supply Circuit)V
Current Rating 11 mA
Termination Type Screw
Number of Outputs 1
Standards Met CAN/CSA C22.2 No.14, IEC/EN 60255-27, IEC/EN 60947-5-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508
Series CM-ENS
Input Type Voltage
IP Rating IP20 (Terminal), IP50 (Housing)
Output Type SPDT Relay
5 In stock for delivery within 5 working day(s)
Price (ex. GST) Each
$ 288.10
(exc. GST)
$ 331.32
(inc. GST)
units
Per unit
1 +
$288.10
Related Products
The VEGAMET 381 is a signal conditioning instrument ...
Description:
The VEGAMET 381 is a signal conditioning instrument that can either power an individual 4→20 mA sensor or taken an input from a device. The VEGAMET shows a measured value that can be scaled by any factor, a display bar ...
A mechanical resonant system kept in resonance by ...
Description:
A mechanical resonant system kept in resonance by an electronic unit. Vibration Rod Level Switch for Free Flowing Solids. Rod Design Prevents Product Bridging. External LED Display Status. Compact and Rugged Design. Relay Output.
Compact ultrasonic sensor for continuous level measurement. Suitable ...
Description:
Compact ultrasonic sensor for continuous level measurement. Suitable for the measurement of liquids and solids in virtually all industries, particularly in the water and waste water sector. Transducer of PVDF with EPDM seal and integrated temperature sensor for correction of ...
Simens CLS100 Pointek range provide accurate, reliable, repeatable ...
Description:
Simens CLS100 Pointek range provide accurate, reliable, repeatable level detection. Inverse frequency shift technology uses the inverse relationship between capacitance frequency to monitor fluid level. Small changes in level result in a large change in frequency resulting in excellent accuracy. ...