- RS Stock No.:
- 122-8556
- Mfr. Part No.:
- FLK-1663/FVF AU
- Brand:
- Fluke
- RS Stock No.:
- 122-8556
- Mfr. Part No.:
- FLK-1663/FVF AU
- Brand:
- Fluke
Technical data sheets
Legislation and Compliance
RoHS Status: Not Applicable
- COO (Country of Origin):
- SG
Product Details
FLUKE Multifunction Tester, Autotest Feature, ±5% Measurement Accuracy - 1660 Series - FLK-1663/FVF AU
To make sure your machine wiring's safe and sound, give it the once over with this multifunction tester from FLUKE. The unit's on hand to check the voltage, frequency and earth resistance of your equipment. A built-in phase sequence test and indicator help clue you in on the current phase in your multiphase electrical system. Want to confirm that your RCD's in tip-top shape and able to stand up to current faults in your circuit? Use this device's automatic RCD test to put it through its paces.
Features & Benefits
• Voltage measurement range between 50 and 1,000V AC/DC for versatile operation
• Measurement accuracy of ±5% for reliable performance
• Built-in USB interface for easy connection to external systems
• Data is downloadable for convenient transfer and retrieval
• Measurement accuracy of ±5% for reliable performance
• Built-in USB interface for easy connection to external systems
• Data is downloadable for convenient transfer and retrieval
Applications
• Manufacturing industry
• Control panels
• Construction sites
• Power stations
• Control panels
• Construction sites
• Power stations
Why should I check the insulation resistance of my wiring?
Measuring the insulation resistance of your wiring lets you test for possible current leakage of your conductors, which helps to prevent fire and electric shocks. As this tester has a range between 20 and 1,000MΩ, you can check for low and high levels of insulation resistance in your cables.
Specifications
Attribute | Value |
---|---|
Loop Impedance Test Type | Phase to Earth, Phase to Neutral |
Automatic RCD Test | Yes |
RCD Ramp Test | Yes |
Model Number p | 1663 |
Non-Tripping | Yes |
Insulation Test Voltage | 50 V, 100 V, 250 V, 500 V, 1000V |
Maximum Voltage Measurement | 500V ac/dc |
Test Type | Automatic RCD Test Sequence, Continuity, Continuity at L-N/N-PE Inputs, Earth Resistance, Frequency, Insulation Resistance, Loop & Line Resistance, Measure Motor Windings with Continuity Test, Measures Trip Time & Current for RCD Type A & AC in One Test, Phase Sequence Test, Prospective Earth Fault Current, Prospective Short-Circuit Current, RCD Trip Current, RCD Trip Time, RCD Variable Current, Resistance, Test Smooth DC Sensitive RCDs, Voltage, Wiring Polarity Checker |
Earth Resistance Measurement | Yes |
Downloadable Data | Yes |
Interface Type | USB |
Continuity Test Current | 10mA |
RCD Test Type | A/F, AC, B/B+, G, S |
Remote Switch Mode | Yes |
IP Rating | IP40 |
Dimensions | 100 x 250 x 125mm |
Minimum Continuity Resistance | 20Ω |
Height | 125mm |
Weight | 1.3 (with Battery)kg |
Safety Category Level | CAT III, CAT IV |
Safety Category Voltage | 300 V, 500 V |
Battery Type | AA |
Safety Category | CAT III 500 V, CAT IV 300 V |
Display Type | LCD |
Plug Type | Australia, New Zealand |
Maximum Continuity Resistance | 2000Ω |
Power Source | Battery |
Width | 250mm |
Length | 100mm |