Product Details

G9SB, Safety Relays, Ultra Slim

The Omron G9SB series is an ultra slim safety relay available in either a 17.5mm or 22.5mm housing. The 17.5mm units have 2 or 3 safety contacts and the 22.5mm units have 3 safety contacts and an auxiliary contact.

1 and 2 input channel units
Manual and automatic reset units
Certification up to category 4 according to EN954-1 (depending on the application)
Can also be used with safety sensors F3SN, F3SH, F3S-B, F3STGR, F3SL, F3S-J
Conforms to EN standards (TUV approval)

Note

When ordering take note of the safety reset mode that is required: Models G9SB**A and G9SB ** B = Auto Reset operation; Models G9SB ** D = Manual Reset operation

Approvals

EN954-1, EN60204-1, UL508, CSA C22.2 No. 14

G9SB Ultra Slim Safety Relays.

• Ultra slim relay module.
• Models with a width of 17.5 mm are available with 2 or 3 poles (safety contacts).
• Models with a width of 22.5 mm with 3 poles (safety contacts).
• 1 and 2 input channels.
• Manual and automatic reset.
• Can be DIN rail mounted.
• Relays with inverse inputs are used when inputting signals from 2 mechanical switches.
• Relays with positive commons are used when inputting signals from a safety sensor or one mechanical switch.
• Conform to EN standards (TUV approval).
• G9SB-3010 is applied to safety category 3 of EN 954-1 if double breaking is used.

Applicable to Safety Sensors.

• Model F3S-B
• Model F3SH
• Model F3S-J
• Model F3SL
• Model F3SN
• Model F3S-TGR Model F3S-TGR Safety Sensors covers a range of articles available within Non-Contact Safety Switches, Light Curtains, Light Beams and Machine Guarding Accessories.

G9SB-3010 DC24 Slim Safety Relay.

• Main contact 3PST-NO (normally open).
• Auxiliary contact SPST-NC (normally closed).
• Direct breaking. (Safety category 3 of EN 954-1 is applied if double breaking is used)
• Auto-reset.
• Rated voltage 24 V dc.
• Operating voltage range 85% to 110% of the rated power supply voltage.
• Power consumption 1.7 W max.
• Input current 60 mA max.
• Resistive load
• Rated load 250 V ac, 5 A. 30 V dc, 5 A.
• Rated carry current 5 A.

Features and Benefits.

• Contact resistance 100 mΩ
• Insulation resistance 100 MΩ mon (at 500 V dc)
• Vibration resistance 10 to 55 to 10 Hz, 0.375 mm single amplitude (0.75 mm double amplitude)
• Shock resistance destruction 300 m/s².
• Shock resistance malfunction 100 m/s²
• Failure rate (P Level) (reference value) 5 V dc, 1 mA
• Always turn OFF the G9SB before connecting an expansion unit.
• If mounting multiple units next to each other the rated current will be 3 A. (do not apply any higher currents)
• Stranded wire 0.2 to 2.5 mm²
• Solid Wire 0.2 to 2.5 mm²
• Screw torque of 0.5 to 0.6 Nm. (incorrect screw tightening can result in a malfunction or generate heat).
• Positive thermistor built onto the circuits detecting short breakdowns.
• Weight 135 g

Applications Include.

• Light curtain.
• Light guard.

Specifications
Attribute Value
Supply Voltage 24 V dc
Number of Channels 2
Auxiliary Contacts 1
Function Emergency Stop
Safety Contacts 3
Length 100mm
Depth 112mm
Width 18mm
9 In stock for delivery within 5 working day(s)
Price (ex. GST) Each
$ 747.25
(exc. GST)
$ 859.34
(inc. GST)
units
Per unit
1 - 2
$747.25
3 - 4
$560.45
5 +
$448.35
Related Products
Each mini. Twin stick contains both the sender ...
Description:
Each mini. Twin stick contains both the sender and receiver elements, each symmetrically mounted in one half of a housing and separated by a central synchronisation beam. The diagram shows two identical mini. Twin units offset by 180° working as ...
The SIRIUS 3TK28 30 Expansion Units are used ...
Description:
The SIRIUS 3TK28 30 Expansion Units are used to increase the number of contacts that can be used on safety related control units. One enabling contact of the base unit is required to connect the expansion unit. The category of ...
The advantages of using the UE403 in conjunction ...
Description:
The advantages of using the UE403 in conjunction with the M4000 series of light curtains are: local processing of signals (fewer cables, lower installation outlay, more control cabinet space); supply voltage for muting sensors direct from UE403; local IP65 connection ...
The safety relay Re. Ly OSSD2 is an ...
Description:
The safety relay Re. Ly OSSD2 is an evaluation unit for sensors or safety devices with OSSD outputs.The safety relay must only be used within the limits of the prescribed and specified technical data and operating conditions at all times. ...