PR Electronics 3100 Series Isolating Signal Converter, Current Input, Current Output, 16.8 → 31.2V dc Supply,
- RS Stock No.:
- 796-7076
- Mfr. Part No.:
- 3103
- Brand:
- PR Electronics
7 In stock for delivery within 7 working day(s)
Added
Price (ex. GST) Each
$312.02
(exc. GST)
$358.82
(inc. GST)
Units | Per unit |
1 + | $312.02 |
- RS Stock No.:
- 796-7076
- Mfr. Part No.:
- 3103
- Brand:
- PR Electronics
Legislation and Compliance
- COO (Country of Origin):
- DK
Product Details
3100 Type - Isolated Repeater
3103 and 3108 type are for isolation and conversion of standard current signals.
Suitable for galvanic separation of analog current signals and elimination of ground loops and measurement of floating signals.
Suitable for galvanic separation of analog current signals and elimination of ground loops and measurement of floating signals.
Features and Benefits
Repeater for 0-20mA
Response time < 7 ms
Splitter function: 1 in - 2 out (only 3108 type, stock-no. 796-7082)
Simple, no setup needed
Input is protected against overvoltage and polarity error
Inputs and outputs are floating and galvanically separated
Installation in ATEX Ex zone 2 / IECEx Zone 2 / FM division 2
Suitable for environments with high vibration stress, e.g. ships
Slimline housing of 6 mm
Response time < 7 ms
Splitter function: 1 in - 2 out (only 3108 type, stock-no. 796-7082)
Simple, no setup needed
Input is protected against overvoltage and polarity error
Inputs and outputs are floating and galvanically separated
Installation in ATEX Ex zone 2 / IECEx Zone 2 / FM division 2
Suitable for environments with high vibration stress, e.g. ships
Slimline housing of 6 mm
DIP-switch programming
Re-calibration is not needed after changing the DIP-switch range settings. Just change the DIP-switch, cycle the power to the unit and obtain the new, pre-calibrated I/O range. HART programming is enabled for selected devices.
Mounting
Devices can be mounted both vertically and horizontally with no air gap separation required. The devices snap onto a power rail or DIN rail and are easily detached by lifting the bottom lock.
High level of isolation
Safe galvanic isolation of 2.5 kVAC provides high noise immunity and prevents ground loops for accurate delivery of the process signal to your control system.
Device status indicators
A front LED indicates device status, e.g. an error in the set-up, sensor or hardware.
Over voltage- / polarity protection
All terminals can withstand up to ±31.2 VDC and are protected against incorrect supply wiring to ensure safe, error-free installation.
PR Electronics DIN Rail Mounting
Specifications
Attribute | Value |
---|---|
Module Type | Isolated Repeater |
Input Signal Type | Current |
Output Signal Type | Current |
Input Range | 0 → 20.5mA |
Output Range | 0 → 20.5mA |
Supply Voltage | 16.8 → 31.2V dc |
Hazardous Area Certification | ATEX |
Mounting Type | DIN Rail Mount |
Operating Temperature Range | -25 → +70°C |
Series | 3100 |
Minimum Operating Temperature | -25°C |
Maximum Operating Temperature | +70°C |