Dold Frequency Monitoring Relay, SPDT, DIN Rail
- RS Stock No.:
- 181-2792
- Mfr. Part No.:
- MK9143N.38 +/-5Hz UH=AC230V tv=0-20s tan=0-30s
- Brand:
- Dold
Subtotal (1 unit)*
$632.72
(exc. GST)
$727.63
(inc. GST)
FREE delivery for orders over $60.00 ex GST
Temporarily out of stock
- Shipping from 05 January 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units | Per unit |
|---|---|
| 1 + | $632.72 |
*price indicative
- RS Stock No.:
- 181-2792
- Mfr. Part No.:
- MK9143N.38 +/-5Hz UH=AC230V tv=0-20s tan=0-30s
- Brand:
- Dold
Specifications
Technical data sheets
Legislation and Compliance
Product Details
Find similar products by selecting one or more attributes.
Select all | Attribute | Value |
|---|---|---|
| Brand | Dold | |
| Monitoring Application | Frequency | |
| Contact Configuration | SPDT | |
| Mounting Type | DIN Rail | |
| Time Delay | 0 → 20 s, 0 → 30s | |
| Frequency Sensing Range | ±5Hz | |
| Series | MK9143N | |
| Frequency Sensitivity | Overfrequency, Underfrequency | |
| Maximum Frequency Sensed | +5Hz | |
| Minimum Operating Temperature | -20°C | |
| Length | 97mm | |
| Dimensions | 97 x 22.5 x 90mm | |
| Minimum Frequency Sensed | -5Hz | |
| Operating Temperature Range | +60°C | |
| Terminal Type | Screw | |
| Height | 90mm | |
| Width | 22.5mm | |
| Maximum Operating Temperature | +60°C | |
| Select all | ||
|---|---|---|
Brand Dold | ||
Monitoring Application Frequency | ||
Contact Configuration SPDT | ||
Mounting Type DIN Rail | ||
Time Delay 0 → 20 s, 0 → 30s | ||
Frequency Sensing Range ±5Hz | ||
Series MK9143N | ||
Frequency Sensitivity Overfrequency, Underfrequency | ||
Maximum Frequency Sensed +5Hz | ||
Minimum Operating Temperature -20°C | ||
Length 97mm | ||
Dimensions 97 x 22.5 x 90mm | ||
Minimum Frequency Sensed -5Hz | ||
Operating Temperature Range +60°C | ||
Terminal Type Screw | ||
Height 90mm | ||
Width 22.5mm | ||
Maximum Operating Temperature +60°C | ||
- COO (Country of Origin):
- DE
Monitoring of local generator sets and voltage supplies
For precise frequency measuring with fast response time
High disturbance immunity
Separately adjustable trip points and separate outputs for over-
and under frequency (1 or 2 c/o each)
MK 9143N / MH 9143:
Trip points adjustable precisely and reproducible on 10 step rotational switch in the range of ± 0,1 Hz to ± 5 Hz related to 50 or 60 Hz
Nominal frequency 50 or 60 Hz selectable
Fixed hysteresis optimised for trip point
As option one common output for under and over frequency Window-mode (MK 9143N/400 / MH 9143/400)
Variable alarm value in the range of 45 to 65 Hz
Hysteresis adjustable for under- and over frequency separatelyadjustable 0 …20% Common output for under and over frequency Window-mode can be selected
Start up delay 0…30 s selectable
Manual or auto reset selectable
Output relay energized or de-energized on trip selectable for
over frequency
Output relay de-energized on trip for under frequency
Universal frequency measuring input for AC 40 … 550V
Several options for auxiliary supply
LED indicators for auxiliary supply, input frequency, over and
under frequency alarm
For precise frequency measuring with fast response time
High disturbance immunity
Separately adjustable trip points and separate outputs for over-
and under frequency (1 or 2 c/o each)
MK 9143N / MH 9143:
Trip points adjustable precisely and reproducible on 10 step rotational switch in the range of ± 0,1 Hz to ± 5 Hz related to 50 or 60 Hz
Nominal frequency 50 or 60 Hz selectable
Fixed hysteresis optimised for trip point
As option one common output for under and over frequency Window-mode (MK 9143N/400 / MH 9143/400)
Variable alarm value in the range of 45 to 65 Hz
Hysteresis adjustable for under- and over frequency separatelyadjustable 0 …20% Common output for under and over frequency Window-mode can be selected
Start up delay 0…30 s selectable
Manual or auto reset selectable
Output relay energized or de-energized on trip selectable for
over frequency
Output relay de-energized on trip for under frequency
Universal frequency measuring input for AC 40 … 550V
Several options for auxiliary supply
LED indicators for auxiliary supply, input frequency, over and
under frequency alarm
Related links
- Dold Frequency Monitoring Relay DIN Rail
- Dold Frequency Monitoring Relay 15 → 280V ac, DIN Rail
- Dold Monitoring Relay 24 → 240V ac/dc, DIN Rail
- Dold Current Monitoring Relay DPDT, DIN Rail
- Dold Cycle Monitoring Relay 230V ac, DIN Rail
- Dold Phase 3 Phase DIN Rail
- Dold Speed Monitoring Relay DIN Rail
- Dold Standstill Monitoring Relay 3 Phase DIN Rail